Envoy NT9010A Przewodnik Instalacji Strona 29

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
Przeglądanie stron 28
Section 2.2: Changing How the NT9010 Works For Users
25
Bell Squawk During Auto Arm . . . . . . . . . . . . . . . . . . . . . Section [014], Option [2]
Bell Squawk on Exit Delay . . . . . . . . . . . . . . . . . . . . . . . . Section [014], Option [3]
Bell Squawk on Entry Delay . . . . . . . . . . . . . . . . . . . . . . . Section [014], Option [4]
Audible Exit Delay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Section [014], Option [6]
Audible Exit Fault. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Section [013], Option [6]
Exit Delay Termination . . . . . . . . . . . . . . . . . . . . . . . . . . . Section [014], Option [7]
2.2.8 Bell Options When the system goes into alarm, the siren will sound. The siren will silence after
the number of minutes programmed for the Bell Cut-off time have passed.
The system supervises the remote sounder. If an open condition is detected, the
system will immediately indicate a trouble condition by beeping the keypad twice
every 10 seconds to alert users to the problem.
If the Temporal Three Fire Signal option is enabled, all Fire signals will follow the
Temporal Three Pattern as described in NFPA 72. If turned OFF all Fire signals will
sound a one second on, one second off cadence.
If Fire Bell Continuous is enabled, the alarm output will sound until a code is
entered. If disabled, the alarm will sound until a code is entered or the bell cut-off
time has expired.
NOTE:Only fire zones will follow the Temporal Three Fire Signal.
Bell Cut-off . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Section [005]
Temporal Three Fire Signal Enable/Disable . . . . . . . . . . . . Section [013], Option [8]
Fire Bell Continuous. . . . . . . . . . . . . . . . . . . . . . . . . . . . . Section [014], Option [8]
2.2.9 User
Commands
[*] [1] Zone Bypassing
Users can bypass individual zones using the [][1] keypad command. This command
can be used if users want to have access to an area while the system is armed, or to
bypass a defective zone (bad contact, damaged wiring) until service can be provided.
A bypassed zone will not cause an alarm. Instructions on zone bypassing can be
found in the NT9010 User’s Guide (“Zone Bypassing”).
When the system is disarmed, all zones bypassed using [][1] will be unbypassed,
except for 24-Hr zones.
If the Code Required for Bypass option is enabled, an access code will be
required to enter the Bypass mode. Only access codes with the Bypass attribute
enabled will be able to bypass zones (see 2.2.2 Access Codes on page 19).
If the Bypass Status Displayed While Armed option is chosen, the System light
will be ON while the system is armed to indicate that there are bypassed zones.
NOTE: If a 24 hour zone is bypassed, ensure that the zone is restored or dis-
abled before removing the bypass.
Code required for bypass . . . . . . . . . . . . . . . . . . . . . . . . . Section [015], Option [5]
Bypass Displayed While Armed . . . . . . . . . . . . . . . . . . . . Section [016], Option [7]
Przeglądanie stron 28
1 2 ... 24 25 26 27 28 29 30 31 32 33 34 ... 63 64

Komentarze do niniejszej Instrukcji

Brak uwag